Bateria 12V 460W Para UPS
Cells Per Unit 6
Voltage Per Unit 12 V
Capacity 76.7W @ 5minute-rate to 1.6V per cell @25°C (77°F)
Weight Approx . 2.50 Kg (5.51 lbs)
Maximum Discharge current 130 A (5sec)
Internal Resistance Approx . 16.6 mO
Operating Temperature Range Discharge:-15?~50? (5°F~122°F)
Charge:-15?~40? (5°F~104°F)
Storage:-15?~40? (5°F~104°F)
Nominal Operating Temperature Range 25°C ±3°C (77°F ± 5°F)
Float charging voltage 13.5 to 13.8 VDC/unit Average at 25°C (77°F)
Recommended Maximum Charging current limit 3.80A
Equalization Charging Voltage 14.4 to 15.0 VDC/unit Average at 25°C (77°F)
Self Discharge Less than 10% after 90 days, can be stored up to 6 months at 25? (77?)
Terminal F2-Faston Tab 250
Container Material ABS (UL 94-HB) & Flame Retardant (94-V0) available upon request